Catalogs | Building Materials | Scaffolding | Fisufor® masonry reinforcement systems | How to use it

fisufor® APP

How to use it

Description: Reinforce opening
The sides of openings are reinforced with Fisufor® so as to prevent fracture at the corners.

The recommended minimum reinforcement is:
• reinforcement in the 2/3 joints immediately below the parapet and 2/3 courses of bricks above the lintel.
• The reinforcements are inserted within an ideal area of ​​50 cm above and below the opening (figure 3).

Stands
Fisufor® is arranged at the base of the wall for the first 2 joints, preventing the risk of fracture.

Corners
• The corners must be “tied” by cutting and bending one of the parallel wires as shown in the figure.
• The corner’s reinforcement must continue for the entire length of the wall.

Sister joints
For masonry with sister joints, Fisufor® must be inserted in all the joints.
Table of use
ApplicationQuantityArrangement
Load-bearing walls*every 10/20 cm every 20/40 cm every 40/50 cmat the base (from 0 to 1 m) in the centre (up to 2 m) at the top (up to 3 m)
Exposed wallsevery 40/50 cmhomogeneous
Walls on foundations3 joints every 40/50 cmat the base along the wall
Concentrated loadsfrom 3 to 5 jointsload bearing
Openings - doors / windows2 joints 2 jointsabove the lintel below the parapet
Sister jointsall jointshomogeneous
Walls and partition walls on slabs2 joints every 40/50 cmat the base along the wall
T-junctionsevery 40/50 cmsymmetrical angles on alternating joints
Fracture controlevery 2 joints every 60 cmat the base along the wall
Connecting cornersevery 40/50 cmalong the wall
Continuous wallsevery 40/50 cmhomogeneous
Changes in the wall widthevery 40/50 cmalong the entire height
Changes in wall height3 jointsat the top of the lowest wall
Double wallsevery jointhomogeneous
Transversal wallsevery 40/50 cmhomogeneous
Cantilevers and pillars4 jointsunder the support frame
* Indicative arrangement. For correct sizing, a structural design is necessary.
-